Highly Visible LCD Display with 2-color ( Red and
Green) LEDs
? Contact, NPN, PNP, or voltage pulse input.
? Front-panel key operation for easy setting.
? Average processing function suppresses flicker.
? Includes scaling, auto-zero time, startup compensation time functions.
? Easy confirmation of max/ min display.
? Short 80-mm depth ( measured from edge of face plate) .
? Finger protective cover ( standard equipment) guards against electric
shock.
? Water- and dust-proof NEMA4X ( IP66 equivalent) front panel.
? Recognized to U.S. and Canadian requirements under the Component
Recognition Program of UL.
? CE marking.
? Built-in external power supply ( 12 VDC, 40 mA) .
Specifications
? Ratings
Model K3MA-F 100-240VDC, K3MA-F-A2 100-240VAC K3MA-F 24VAC/ VDC, K3MA-F-A2 24VAC/ VDC
Supply voltage 100 to 240 VAC 24 VAC/ VDC
Operating voltage range 85% to 110% of the rated supply voltage
Power consumption
( under maximum load)
6 VA max. 4.5 VA max. ( 24 VAC)
4.5 W max. ( 24 VDC)
External power supply 12 VDC, 40 mA
Insulation resistance 20 M min. ( at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Dielectric strength 2, 000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Noise immunity 1, 500 V on power supply terminals in normal or common
mode.
1 s, or 100 ns for square-wave noise with 1 ns.
480 V on power supply terminals in normal mode.
1, 500 V in common mode.
1 s, or 100 ns for square-wave noise with 1 ns.
Vibration resistance Vibration: 10 to 55 Hz, Acceleration: 50 m/ s2
5 min each in X, Y, and Z directions for 10 sweeps.
Shock resistance 150 m/ s2 ( 100 m/ s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
Ambient temperature Operating: 10 C to 55 C ( with no condensation or icing)
Storage: 25 C to 65 C ( with no condensation or icing)
Approved safety standards UL61010-1, CSA C22.2 No.61010-1-04, conforms to EN61010-1 ( Pollution degree 2/ overvoltage category II)
Conforms to VDE0106/ P100 ( finger protection)
EMC ( EMI) EN61326+ A1 Industry
Emission Enclosure: CISPR 11 Group 1 class A: CISRP16-1/ -2
Emission AC Mains: CISPR 11 Group 1 class A: CISRP16-1/ -2
( EMS) EN61326+ A1 Industry
Immunity ESD: EN61000-4-2: 4 kV contact discharge
8 kV air discharge
Immunity RF-interference: EN61000-4-3: 10 V/ m ( amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise: EN61000-4-4: 2 kV ( power line)
Immunity Burst Noise: 1 kV line to line ( I/ O signal line)
Immunity Surge: EN61000-4-5: 1 kV ( power line)
2 kV line to ground ( power line)
Immunity Conducted Disturbance: EN61000-4-6: 3 V ( 0.15 to 80 MHz)
Immunity Voltage Dip/ Interrupting: EN61000-4-11: 0.5 cycle, 0, 180 , 100% ( rated voltage)